All Topics

Startup & Shutdown

Safe boiler startup sequence, normal shutdown, and emergency shutdown procedures.

Cold Startup Sequence

Starting a cold boiler requires a specific sequence to prevent thermal shock and ensure safety.

  • 1. Verify water level is at the normal operating level
  • 2. Open the vent valve (allows air to escape as steam forms)
  • 3. Verify fuel supply is available and valves are in correct position
  • 4. Check all controls: pressuretrol, LWCO, flame safeguards
  • 5. Start the burner on low fire
  • 6. Warm the boiler SLOWLY — avoid thermal shock
  • 7. Close the vent valve when steam appears (positive pressure)
  • 8. Monitor pressure rise — do not exceed MAWP
  • 9. Test safety valve(s) when at 75%+ operating pressure
  • 10. Put the boiler on line gradually — open the steam stop valve slowly

Opening steam valves rapidly causes water hammer in cold steam lines. ALWAYS open slowly.

Normal Shutdown

A controlled shutdown follows a safe sequence to cool the boiler gradually.

  • 1. Reduce firing rate to low fire
  • 2. Allow pressure to drop gradually
  • 3. Close the steam stop valve when boiler is isolated from the header
  • 4. Secure the burner
  • 5. Maintain water level during cooldown
  • 6. Open the vent valve once pressure drops below 5 psi to prevent vacuum
  • 7. Do NOT drain the boiler hot — let it cool naturally

Emergency Shutdown

Emergency shutdown is performed when immediate danger exists.

  • Secure the burner IMMEDIATELY
  • Emergency conditions: low water, overpressure, flame rollout, tube rupture, fuel leak
  • Do NOT add water to an overheated boiler
  • Do NOT drain a hot boiler rapidly
  • Notify supervision and document the incident
  • Boiler must be inspected before returning to service

In any emergency, the FIRST action is always to secure the burner.